(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.

  • Viewed
    Products
  • My
    Components
  • Cart
Recently Viewed Products
X
My Components
X
Cart item(s)
X
Loading...
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

Thermac NEO Temperature Controller (Digital Control Meter) [E5□N/E5□N-H/E5□N-HT] (E5AN-HAA2HH03BF-FLK AC100-240)

Thermac NEO Temperature Controller (Digital Control Meter) [E5□N/E5□N-H/E5□N-HT] (E5AN-HAA2HH03BF-FLK AC100-240)
You can add up to 6 items per a category to the compare list.

Part Number :
    • Starting From :
      17,369₹/Unit
  • Order Qty :
  • Total Price :
    ---
  • Days to ship :
    ---

Select part number to Order Now/ Add to Cart

Product Description

From selection to operation and maintenance, the best-selling temperature controller Thermac NEO series is convincing.
A high-performance type that responds to faster and more accurate temperature and process control, and a program type that expands the range of compatible applications are also available.

Dimensional Drawing of OMRON Temperature Controllers

E5CN-H Temperature Controllers type

Note: The terminal block cannot be removed.

*For information on model numbers other than those listed above, please refer to the digital catalog.

Specification Table of OMRON Temperature Controllers

Temperature Controllers Names of each part

E5CN-H Temperature Controllers type

*For information on Temperature Controllers model numbers other than those listed above, please refer to the digital catalog.

Ratings/Performance of Temperature Controllers

E5CN-H Temperature Controllers type rating

Power supply voltagePower supply voltage: Type without D: AC100-240V 50/60Hz
Power supply voltage: Type with D: AC24V 50/60Hz/DC24V
Allowable voltage fluctuation range85 to 110% of power supply voltage
Power ConsumptionAt 100 to 240 VAC: 8.5 VA (maximum) (E5CN-HR2 3.0 VA at 100 VAC) At 24 VAC/
DC: 5.5 VA (24 VAC) / 3.5 W (24 VDC) (maximum) (E5CN-HR2D 2.7 VA at 24 VAC)
Sensor InputYou can choose from the following (full multi-input).
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: Pt100, JPt100
Current input: 4 to 20mA, 0 to 20mA
Voltage input: 1 to 5V, 0 to 5V, 0 to 10V
Input impedanceCurrent input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting to the ES2-HB-N, use a 1:1 connection.)
Temperature Controllers MethodON/OFF or 2-degree-of-freedom PID (with auto-tuning)
Temperature Controllers OutputRelay Output1a AC250V 3A (resistive load) Electrical life 100,000 times Minimum applicable load 5V 10mA
Voltage output
(for driving SSR)
Output voltage: DC12V±15% (PNP) Maximum load current: 21mA, with short circuit protection circuit
Current OutputDC4~20mA/DC0~20mA Load 600Ω or less Resolution approximately 10,000*
Linear Voltage OutputDC0 to 10V (Load 1kΩ or more) Resolution: Approx. 10,000
Auxiliary OutputScoreMaximum 2 items
Output SpecificationsRelay output 1a AC250V 3A (resistive load) Electrical life 100,000 times Minimum applicable load 5V 10mA
Event InputScoreMaximum 2 points (depending on the model: only types with event input B)
External contact
input specifications
During contact input: ON: 1kΩ or less OFF: 100kΩ or more
Non-contact input: ON: Residual voltage 1.5V or less OFF: Leakage current 0.1mA or less
Current output: Approx. 7mA (per contact)
Simple CalculationNumber of arithmetic expressionsUp to 8 (can be combined via internal auxiliary relays)
Calculations・Logic operation: One of the following four patterns can be selected. Each contact can be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, D are 4 input points).
・Delay: On-delay or off-delay can be set for the result of the above logic operation. Setting time: 0 to 9999 seconds or 0 to 9999 minutes
・Output inversion: possible
output1 internal auxiliary relay per calculation formula
Internal auxiliary
relay allocation
Internal auxiliary relay (simple calculation result) Up to 8 points can be assigned to the following:
Event input operation, auxiliary output, or Temperature Controllers output
Transmission OutputScoreMaximum 1 point (depending on model: type with transmission output F)
Output SpecificationsCurrent output: DC4 to 20mA Load: 600Ω or less Resolution: Approximately 10,000 at 4 to 20mA
RSP Inputnone
Setting methodDigital setting by front keys
Instruction method11-segment digital display and single-light-emitting display (7-segment display also available) Character height PV: 11 mm, SV: 6.5 mm
Bank switching functionAvailable (number of banks: 8)
Local SP, alarm set value, PID group No. (PID constant, upper and lower operation limit, etc.)
Other featuresManual output, heating/cooling Temperature Controllers, loop break alarm function, SP lamp, alarm function, heater break detection function (
including SSR failure and heater overcurrent detection functions), 40% AT, 100% AT, operation amount limit, input digital filter, self-tuning,
temperature input correction, run/stop, protection, control output ON/OFF count function, square root calculation function, operation amount change rate limit,
PV/SV status display function, simple program function, cooling coefficient automatic adjustment function, etc.
Ambient Temperature Controllers-10 to +55°C (but no condensation or freezing) / 3-year warranty: -10 to +50°C
Ambient humidityRelative humidity 25-85%
Storage Temperature Controllers-25 to +65°C (but no condensation or freezing)

* For current output types, Temperature Controllers output 1 can also be used as transmission output.

E5CN-H Temperature Controllers type performance

Indication accuracyThermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit or less*1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit or less
Analog input: ±0.1%FS ±1 digit or less
CT input: ±5%FS ±1 digit or less
Transmission Output Accuracy±0.3%FS or less
Temperature Controllers effect*2Thermocouple input (R, S, B, W, PLII): (±1% PV or ±10°C, whichever is greater) ±1 digit or less
Other thermocouple input: (±1% PV or ±4°C, whichever is greater) ±1 digit or less *3
Platinum resistance thermometer input: (±1% PV or ±2°C, whichever is greater) ±1 digit or less
Analog input: (±1% FS) ±1 digit or less
Voltage effect*2
Effects of electromagnetic interference
(according to EN61326-1)
Input Sampling Period60ms
Adjustment SensitivityTemperature input: 0.1 to 3240.0°C or °F (in 0.1°C or °F units)
Analog input: 0.01 to 99.99% FS (in 0.01% FS units)
Proportional band (P)Temperature input: 0.1 to 3240.0°C or °F (in 0.1°C or °F units)
Analog input: 0.1 to 999.9% FS (in 0.1% FS units)
Integration time (I)0.0 to 3240.0 s (in 0.1 s units)
Differential time (D)0.0 to 3240.0 s (in 0.1 s units)
Control Period0.5, 1 to 99 s (in 1 s increments)
Manual Reset Value0.0 to 100.0% (in 0.1% increments)
Alarm Setting Range-19999 to 32400 (decimal point position depends on input type)
Effect of signal source resistanceThermocouple: 0.1℃/Ω or less (100Ω or less), Platinum resistance thermometer: 0.1℃/Ω or less (10Ω or less)
Insulation resistance20MΩ or more (at DC500V megger)
Withstand voltage2,300V AC, 50 or 60Hz, 1min (opposite polarity live terminals)
vibrationmalfunction10~55Hz 20m/s2 3 axis direction 10min
Durability10 to 55Hz, half amplitude 0.75mm, 3 axial directions 2h
impactmalfunction100m/s23 axial directions, 3 times each
Durability300m/s23 axial directions, 3 times each
massMain unit: Approx. 150g Mounting tool: Approx. 10g
Protective structureFront: IP66, Rear case: IP20, Terminal: IP00
Memory ProtectionNon-volatile memory (number of writes: 1 million times)
Configuration ToolCX-Thermo Ver.4.0 or later
Configuration tool portBottom of E5CN-H: Use the USB-serial conversion cable E58-CIFQ1 to
connect the USB port on the computer to the port on the bottom of the E5CN-H. *4
Temperature Controllers standardCertification StandardsUL61010-1, CSA C22.2 No.1010-1
Compliance standardsEN61010-1 (IEC61010-1): Pollution degree 2, Overvoltage Category II, Lloyd's Standard*5
EMC DirectiveEMI EN61326-1 *6Radiated
interference field strength EN55011 Group1 class ANoise
terminal voltage EN55011 Group1 class
AEMS EN61326-1 *6Electrostatic
discharge immunity EN61000-4-2Electromagnetic
field strength immunity EN61000-4-3Burst
noise immunity EN61000-4-4Conducted
interference immunity EN61000-4-6Surge
immunity EN61000-4-5Power
frequency magnetic field immunity EN61000-4-8Voltage
dip/interruption immunity EN61000-4-11

*1.K (-200 to 1300°C range), T, N below -100°C and U, L are within ±2°C ±1 digit. B below 400°C is not specified. B from 400 to 800°C is within ±3°C.
    R, S below 200°C is within ±3°C ±1 digit. W is within (±0.3% PV or ±3°C, whichever is greater) ±1 digit.
    PLII is within (±0.3% PV or ±2°C, whichever is greater) ±1 digit.
*2.Conditions: Ambient Temperature Controllers: -10℃ to 23℃ to 55℃ Voltage range: -15 to +10% of rated voltage
*3.K sensor -100℃ or less is within ±10℃
*4.External serial communication (RS-232C or RS-485) and cable communication for setting tool can be used simultaneously
*5.For compliance with Lloyd's standards, see "Compliance with marine standards" on page 144 of the digital catalog
*6.Industrial electromagnetic environment (EN/IEC61326-1 Table 2)

*For information on For information on model numbers other than those listed above, please refer to the digital catalog model numbers other than those listed above, please refer to the digital catalog.

Part Number
E5AN-HAA2HH03BF-FLK AC100-240
Part NumberPriceMinimum Order Qty.Volume DiscountDays to ShipInput Method Output Type Number of Control Points Setting Method Failure Detecting Function Power Supply Voltage
(V)
Control Output 1 Control Output 2 Option Event Input
(Point)
Heater burnout / SSR failure / heater overcurrent detection function Program type Specifications Communication Transmission Output

₹ 40,534.33

1 Piece(s) 93 Day(s) Thermocouple / Platinum temperature measuring resistor---Heater Breakage / Heater Over current / SSR Breakdown100 to 240 VACOutput Unit MethodOutput Unit MethodWith RS-485 communication2Detection for single or three-phase heater----

Loading...

  1. 1
 

Basic Information

Control Method ON/OFF Control / PID control with auto tuning Number of Input Points(pcs.) 1 Case color Black
Auxiliary output points 2

Please check the type/dimensions/specifications of the part E5AN-HAA2HH03BF-FLK AC100-240 in the Thermac NEO Temperature Controller (Digital Control Meter) [E5□N/E5□N-H/E5□N-HT] series.

Product variants

Part Number
E5AN-HAA2HB AC100-240
E5AN-HAA2HH01BF-FLK AC100-240
E5AN-HAA2HHBB AC100-240
E5AN-HAA2HHBF AC100-240
E5AN-HPRR2BB AC100-240
E5AN-HTAA2HB AC100-240
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipInput Method Output Type Number of Control Points Setting Method Failure Detecting Function Power Supply Voltage
(V)
Control Output 1 Control Output 2 Option Event Input
(Point)
Heater burnout / SSR failure / heater overcurrent detection function Program type Specifications Communication Transmission Output

₹ 36,058.00

1 Piece(s) 5 Day(s) Platinum temperature measuring resistor / Thermocouple---Heater Over current / SSR Breakdown / Heater Breakage100 to 240 VACOutput Unit MethodOutput Unit Method-2Detection for single-phase heater----

₹ 40,645.51

1 Piece(s) 9 Day(s) Voltage / Current / Platinum temperature measuring resistor / ThermocoupleCurrent / Linear Voltage / SSR Drive Output Voltage / Relay contact2RSP Input / Key inputHeater Over current / SSR Breakdown / Heater Breakage100 to 240 VACOutput Unit SystemOutput Unit System-2Detection for single or three-phase heater-96×96 mm high-performance typeRS-232C, CompoWay/F1

₹ 33,897.35

1 Piece(s) 9 Day(s) Platinum temperature measuring resistor / Thermocouple---Heater Over current / SSR Breakdown / Heater Breakage100 to 240 VACOutput Unit MethodOutput Unit Method-4Detection for single or three-phase heater----

₹ 36,310.90

1 Piece(s) 5 Day(s) Platinum temperature measuring resistor / Thermocouple---Heater Over current / SSR Breakdown / Heater Breakage100 to 240 VACOutput Unit MethodOutput Unit Method-2Detection for single or three-phase heater----

₹ 48,180.00

1 Piece(s) 5 Day(s) Platinum temperature measuring resistor / Thermocouple----100 to 240 VACRelay Output for Position ProportionalRelay Output for Position Proportional-------

₹ 36,058.00

1 Piece(s) 5 Day(s) Voltage / Current / Platinum temperature measuring resistor / Thermocouple---Heater Over current / SSR Breakdown / Heater Breakage100 to 240 VACOutput Unit MethodOutput Unit Method-2Detection for single-phase heaterBlack type, three-stage display---
X
whatsapp-qr whatsapp-icon